| Light-duty receptacle loads |
15 A, 120 V, single-phase |
12 AWG copper |
Approximately 4.9% at 15 A |
Portable tools, task lighting, chargers, and small office equipment |
Use a shorter branch circuit or move up to 10 AWG when sensitive equipment or motor starting is expected. |
| General-purpose construction receptacles |
20 A, 120 V, single-phase |
8 AWG copper for a 3% target |
Approximately 2.6% at 20 A |
Hand tools, small saws, lighting strings, and temporary work areas |
A 12 AWG conductor may satisfy ampacity for a 20 A circuit but can exceed the commonly recommended 3% voltage-drop target on a long run. |
| Moderate single-phase equipment |
30 A, 120 V, single-phase |
6 AWG copper for a 3% target |
Approximately 2.5% at 30 A |
Welders with suitable ratings, larger tools, pumps, and temporary equipment feeders |
Confirm the equipment nameplate, overcurrent protection, starting current, and receptacle configuration before selecting the conductor. |
| Higher-capacity single-phase equipment |
40 A, 120 V, single-phase |
4 AWG copper for a 3% target |
Approximately 2.1% at 40 A |
Large temporary equipment and dedicated branch circuits |
Verify terminal temperature ratings, conductor insulation rating, grounding requirements, and the pole’s available fault-current rating. |
| Short branch circuit, low continuous load |
15–20 A, 120 V, single-phase |
12 AWG copper may be suitable when the run is short |
Depends on length and operating current |
Nearby receptacles located close to the temporary power pole |
Calculate voltage drop using the actual one-way length. The 3% target is easier to meet when the branch-circuit distance and load are reduced. |
| Long feeder from service or generator to the pole |
Determined by calculated load |
Size from ampacity, voltage drop, installation method, and overcurrent protection |
Evaluate feeder and branch-circuit drop together |
Remote jobsite distribution, multiple temporary poles, or generator-fed layouts |
Design for approximately 5% maximum total voltage drop where practical: about 2% on the feeder and 3% on the branch circuit. |
| Recommended design target |
Any branch-circuit rating |
Choose the conductor that keeps calculated branch-circuit voltage drop at or below 3% |
Maximum target at 120 V: 3.6 V |
Reliable temporary receptacles and reduced motor-starting problems |
NEC voltage-drop guidance is generally presented in Informational Notes rather than as a universal mandatory limit. Always comply with applicable adopted codes and the authority having jurisdiction. |
| Example calculation: Voltage drop for a single-phase circuit can be estimated with VD = 2 × K × I × D ÷ CM, where K is the conductor resistivity constant, I is current in amperes, D is one-way distance in feet, and CM is conductor circular-mil area. The examples above use copper conductors, approximately 100 ft one-way, 120 V, and resistance-based estimates at near-ambient conditions. |