| 2/2 Normally Closed (NC) | Two ports and two positions: inlet and outlet. | Inlet and outlet are closed; flow is shut off. | Inlet and outlet are connected; flow passes through the valve. | Water, air, gas, fuel, lubrication, cooling, dispensing, and safety shutoff circuits. | Choose this function when the valve should stop flow automatically if electrical power is lost. |
| 2/2 Normally Open (NO) | Two ports and two positions: inlet and outlet. | Inlet and outlet are connected; flow passes through the valve. | Inlet and outlet are closed; flow is shut off. | Continuous cooling, ventilation, purge, bypass, and systems that must flow during a power failure. | Choose this function when continued flow is preferred or required during loss of electrical power. |
| 3/2 Normally Closed (NC) | Three ports and two positions, commonly supply (P), outlet/actuator (A), and exhaust (R). | P is blocked; A is connected to R, so the actuator/output side is exhausted. | P is connected to A; R is blocked, so the actuator/output side is supplied. | Single-acting pneumatic cylinders, spring-return actuators, clamps, grippers, and pilot control circuits. | Use when the output must be vented and the actuator must return to its spring position when power is removed. |
| 3/2 Normally Open (NO) | Three ports and two positions, commonly supply (P), outlet/actuator (A), and exhaust (R). | P is connected to A; R is blocked, so the output side is supplied. | P is blocked; A is connected to R, so the output side is exhausted. | Single-acting actuators that should remain pressurized or active when electrical power is unavailable. | Use when the actuator should be supplied in the normal, de-energized condition and vented after energizing. |